ОтоплениеIVAR#IVAR#Heating and air-conditioning systems#Components for heating systems#Heat meters#Construction
EQUIMETER - Теплометр
EQUIMETER is a compact three-way metering module which offers the option to regulate both supply and by-pass section by exploiting the flow reading of the heat meter, simplifying hydraulic balancing operations. Available in two power/flow rate variants, it houses a 1.5 m³/h or 2.5 m³/h heat meter, while still keeping the main G 3/4” flat seal connections to the upright columns and to the utilities. EQUIMETER can be supplied on a frame or in a box, pre-assembled or in a jig with separate components.
MC is a classical pre-assembled module intended to meet high flow rate requirements thanks to the low hydraulic resistance of the circuit. MC is available in two power/flow rate variants, with different corresponding connections to the upright columns and to the utilities: MC1 has G 1” connections and can house heat meters from 2.5 m³/h. MC2 is equipped with G 1” 1/4 connections and can house larger meters with G 1” 1/4 connections and a nominal flow rate of 3.5 or 6.0 m³/h. Heat module and domestic water module are on different frames and can be built according to requirements.
Domestic water lines can be customized and allow up to three displacement meters to be installed, or up to two by adding a thermostatic blender.
All the electronic components are supplied separately, chosen depending on the individual installations thanks to a complete range of meters for direct reading on individual devices or concentration of data at a single reading point by means of M-BUS or RADIO protocol.
Equimeter
As concerns measurement devices, it is possible to choose among different kits suitable to any type of reading (direct, central via M-BUS or central via RADIO network). All devices are MID compliant and feature supplementary metrology marking.
Special configurations
Each building is characterised by different spaces, constraints and installation solutions. For this reason, IVAR technical department can design special configurations upon request, beyond the standard range of modules listed in the catalogue, like metering modules with downward connections, multiple connection recessed closets equipped with risers, cabinets complete with distribution manifolds, mixing valves, booster groups: IVAR makes EQUIMETER a flexible element suitable to all configurations.
Technical features
Max static working pressure: 10 bar
Max differential pressure across the zone valve: 0.9 bar
Max working temperature: 90 °C
Connections to piping system: G ¾''
Connections to metering devices:
- G ¾”, port-to-port distance110 mm (EQM1)
- G1”, port-to-port distance130 mm (EQM2)
Rainwater and domestic hot/cold water meters nominal flow rate: 1.5 m3/h
Heat meter nominal flow rate:
- EQM 1 and realtive variants:1.5 m3/h
- EQM 2 and relative variants: 2.5 m3/h
Module pressure drops (including suggested heat meters):
- EQM1: Kv = 2.25
- EQM2: Kv = 2.75
Further info from manufacturer on EQUIMETER IVAR